Galaxy VL | Features |
Nominal power rating (kVA = kW) | 200, 300, 400, 500 |
Scalability | From 200 kW to 500 kW with 50 kW power module increments |
N+1 power ratings | Up to 450 kW N+1 |
Technical rating | 500 kW |
Topology | On-line double conversion, UL-verified eConversion |
Key features | |
Modular design | Power module, control module, power supply unit |
Third-party verified
Live Swap |
Power Module |
Display | 7-inch color touch display, mimic diagram on display |
Cabinet Type | Standalone, White (RAL9003) |
Efficiency | |
Double conversion mode | > 97% |
eConverison mode | Up to 99% |
ECO mode | Up to 99% |
Input | |
Rated voltage | 380/400/415/440/480 VAC |
Input voltage range
(phase to phase) |
331-552 V |
Single mains/dual mains | Single mains as standard. Easily converted to dual mains. |
Input current total harmonic distortion (THDI) | <3% |
Input power factor | >0.99 at load >25% |
Cable entry | Top as standard. Optionable bottom cable entry cabinet available. |
Input backfeed protection |
Input backfeed protection: Included. Bypass backfeed protection: External or internal with kit. |
Maximum short-circuit rating | 65 kA Icw |
Output | |
Nominal output voltages | 380/400/415/440/480 VAC |
Load power factor | PF=1 @ 40 °C (104 °F) without derating |
Voltage regulation | +/- 1% (symmetrical load) |
Frequency | 50/60Hz +-0.1% free running |
Overload normal operation |
1 min @ 150%; 10 min @ 125%
(110% continuous at 30 °C (86°F)) |
Overload battery operation | 1 min @ 125% |
Output THDU on linear load | <1% |
Output THDU on non-linear load | <3% |
Output Voltage classification | VFI-SS-111 |
Paralleling | |
Parallel capability | Parallelable for capacity (3 MW) or redundancy (2.5 MW N+1) |
Batteries | |
Battery type | VRLA/Lithium-Ion/NiCad |
DC Bus/Number of VRLA battery blocks | 480-576 V (40-48 blocks) |
Float Voltage, 2.27 V/cell | 545-654 V |
Backup time | 5 minutes to 1 hour (longer runtime available*) |
Maximum charging power (0-40% load) | 80% |
Maximum charging power (100% load) | 20% |
Number of supported battery breakers | 4 |
Breaker trip function | UV coil on the battery breaker |
Temperature compensation | -3.3 mV/°C/cell, for T >= 25 °C 0 mV/°C/cell, for T < 25 °C |
Maximum short-circuit level | 30 kA |
Battery test | Manual/automatic (selectable) |
Battery runtime estimation | Yes |
Battery deep discharge protection | Yes |
Environment | |
Operating temperature | 0-40 °C without rating |
Storage temperature | -25 ° to 55 °C (-13-131 °F) |
Humidity | 0% to 95% |
Elevation/altitude | 1000m 100% load
up to 3000m with derating |
Audible noise at 100% load | 400 V: 69.5 dB; 480 V: 68 dB |
IP level (Ingress Protection) | IP20 |
Dust |
Supports harsh environments Pollution degree 2 (IEC 62040). Air filter included. |
Conformance coating | On PCBA |
Dimensions | |
200-500kW UPS (HxWxD) | 1970 x 850 x 925 mm
(77.6 x 33.5 x 36.4 in) |
Weight | 200 kW UPS: 495 kg (1091 lb);
500 kW UPS: 720 kg (1587 lb) |
Options and accessories | |
Lithium-ion battery cabinet | Parallel communications kit |
Maintenance bypass cabinet | Network management card |
Bottom cable entry cabinet | Internal backfeed kit |
Battery breaker kit | Kirk key kit (480 V)* |
Air filter kit | 600 V:480 V transformer cabinet (Canada) |
Seismic kit | Classic battery cabinet (400 V)* |
Common VRLA battery bank | Battery breaker box (400 V)* |
Remote alarm panel |